Opportunity
Stack temp- 240 deg c
Efficiency – 88 %
Losses – Dry flue gas loss- 8.8 % ( 8%)
Moisture loss – 2.2 % (10.7%)
Unburnt loss – 0.5 % (0.5%)
Radiation loss – 0.5 % (0.5%)
Challenges
Reduction in heat transfer Performance
Low end corrosion
Conventional heat recovery system
Air preheater – 4%
Economiser/Water preheater – 4%
Limitations of conventional system
It targets only sensible heat loss.
Low end corrosion limits heat recovery opportunity
Heat recovery opportunity (Extra)
Sensible heat loss- 6.5 %
Latent heat loss – 8 %
Gaseous fuel
Higher hydrogen contents- Higher latent heat recovery (Efficiency can approach 105%)
Less flue-gas volume- Less heat transfer area requirement & higher pay back
Less sulphur- Less severity of corrosion & higher freedom for material selection
Higher availability of the boiler as condensing heat exchanger system is independent of remaining boiler system and does not interfere with normal boiler operation.
Condensing economiser can be independently sized depending on makeup water quantity